Product Overview
The LEM HAT 200..1500-S is a Hall effect current transducer designed for electronic measurement of DC, AC, and pulsed currents with galvanic separation between primary and secondary circuits. It features an insulating plastic case, easy installation, low power consumption, and a compact, space-saving design suitable for a wide range of current ratings. Its high immunity to external interference makes it ideal for industrial applications.
Product Attributes
- Brand: LEM
- Material: Insulating plastic case recognized according to UL 94-V0
- Certifications: EN 50178: 1997, UL 508: 2010 (UL conform only applicable @ TA = - 40 C .. + 85 C)
- Application Domain: Industrial
Technical Specifications
| Type | Primary nominal rms current measuring range (IPN) | Primary current, RoHS since date code | Supply voltage ( 5 %) (UC) | Current consumption (IC) | Insulation resistance @ 500 V DC | Output voltage (Analog) @ IPN, RL = 10 k, TA = 25 C (Vout) | Output internal resistance (Rout) | Load resistance (RL) | Accuracy @ IPN, TA = 25 C (excluding offset) | Linearity error (L) (0 .. IPN) | Electrical offset voltage (VOE) @ TA = 25 C | Hysteresis offset voltage (VOH) @ IP = 0, after an excursion of 1 x IPN | Temperature coefficient of VOE (- 40 C .. + 80 C) | Temperature coefficient of VOE (+ 80 C .. + 105 C) | Temperature coefficient of Vout (% of reading) (TCVout) | Step response time to 90 % of IPN (tr) | di/dt accurately followed | Frequency bandwidth (BW) (- 3 dB) | Ambient operating temperature (TA) | Ambient storage temperature (TS) | Mass (m) | Ud Rms voltage for AC insulation test, 50 Hz, 1 min | W Impulse withstand voltage 1.2/50 s | Min dCp Creepage distance | dCI Clearance | CTI Comparative tracking index (group IIIa) |
| HAT 200-S | 200 A | 600 A (47143) | 15 V | 15 mA | > 1000 M | 4 V | 100 | > 10 k | 1 % of IPN | 1 % of IPN | < 20 mV | < 10 mV | < 1 mV/K | < 1.5 mV/K | < 0.1 %/K | < 5 s | > 50 A/s | DC .. 25 kHz | - 40 .. + 105 C | - 40 .. + 105 C | 300 g | 4.9 kV | > 9.9 kV | 11 mm | 11 mm | 275 |
| HAT 400-S | 400 A | 1200 A (46115) | ||||||||||||||||||||||||
| HAT 500-S | 500 A | 1500 A (46129) | ||||||||||||||||||||||||
| HAT 600-S | 600 A | 1800 A (46115) | ||||||||||||||||||||||||
| HAT 800-S | 800 A | 2400 A (46115) | ||||||||||||||||||||||||
| HAT 1000-S | 1000 A | 2500 A (46097) | ||||||||||||||||||||||||
| HAT 1200-S | 1200 A | 2500 A (77271) | ||||||||||||||||||||||||
| HAT 1500-S | 1500 A | 2500 A (46158) |