Online Service

Online Service

Contact Person
+86 136 6733 2386
quality Industrial current sensor LEM LT58-S7SP1 with compensated closed loop design and UL 94V0 insulated casing factory
<
quality Industrial current sensor LEM LT58-S7SP1 with compensated closed loop design and UL 94V0 insulated casing factory
>
Specifications
working temperature:
-10℃~+70℃
Current Range:
±70A
Band Width:
100kHz
Bidirectional Current Detection:
Support
Mfr. Part #:
LT58-S7/SP1
Key Attributes
Model Number: LT58-S7/SP1
Product Description

Product Overview

The LT 58-S7/SP1 is an insulated current sensor utilizing the Hall effect principle for measuring DC, AC, and pulsed currents. It offers high accuracy, excellent linearity, low temperature drift, and a wide frequency bandwidth, making it suitable for various industrial applications. The sensor features a closed-loop (compensated) design and is housed in a UL 94-V0 insulating casing.

Product Attributes

  • Brand: LEM
  • Origin: Beijing, China
  • Certifications: prEN 50178, UL 94-V0

Technical Specifications

ParameterDescriptionValueUnit
Product NameCurrent SensorLT 58-S7/SP1
Primary Rated RMS Current (IPN)Primary rated effective value current50A
Primary Current Measurement Range (IP)Primary current, measurement range0 .. 70A
Measuring Resistance (RM)@ 12 V0 .. 140
@ 15 V0 .. 200
Secondary Rated RMS Current (ISN)Secondary rated effective value current50mA
Conversion Ratio (KN)Conversion rate1 : 1000
Supply Voltage (VC)Power voltage ( 5 %) 12 .. 15V
Current Consumption (IC)Current consumption @ 12V28 + ISmA
AC Insulation Test Voltage (Vd)Effective voltage for AC insulation detection (50 Hz, 1 min)6kV
Overall Accuracy (XG)Total accuracy @ IPN, TA = 25C 0.8%
Linearity (L)Linearity< 0.2%
Zero Offset Current (IO)Zero offset current @ TA = 25C 0.2mA
Magnetic Offset Current (IOM)Magnetic offset current @ IP = 0, overload through IPN 0.1mA
Offset Current Temperature Drift (IOT)(- 10C .. + 70C) 0.35mA
0.64mA
Response Time (tra)Reaction time @ 10 % of IP max< 500ns
Response Time (tr)Response time @ 90 % of IP max< 1s
di/dt Following Accuracydi/dt following accuracy> 100A/s
Bandwidth (f)Bandwidth (- 3 dB)DC .. 100kHz
Operating Temperature (TA)Environment operating temperature- 10 .. + 70C
Storage Temperature (TS)Environment storage temperature- 25 .. + 80C
Secondary Coil Resistance (RS)Secondary coil resistance @ TA = 70C11
MassMass68g
Primary Conductor Temperature LimitPrimary conductor temperature not to exceed100C

Advantages

  • Excellent accuracy
  • Good linearity
  • Low temperature drift
  • Optimal response time
  • Wide frequency bandwidth
  • No insertion loss
  • Strong immunity to interference
  • Current overload capability

Applications

  • AC variable frequency drives, servo motors
  • DC motor traction, static converters
  • Battery power supplies
  • Uninterruptible Power Supplies (UPS)
  • Switch Mode Power Supplies (SMPS)
  • Welding machine power supplies

Mechanical Features

  • Natural tolerance: 0.5 mm
  • Fastening points: 2 holes 5.4 mm
  • Primary aperture: 20 mm
  • Secondary connection: Clamp terminals

Notes

  • IS is positive when flowing in the direction of the arrow on IP.
  • Dynamic performance (di/dt and response time) is optimal when the busbar completely fills the primary aperture.
  • This module is a standard sensor. For different applications (supply voltage, turns ratio, single-phase measurement, etc.), please contact us.