Online Service

Online Service

Contact Person
+86 136 6733 2386
quality High Accuracy CYBERSEN CHT-DS-I Duct Temperature and Humidity Transmitter for Instrument Integration factory
<
quality High Accuracy CYBERSEN CHT-DS-I Duct Temperature and Humidity Transmitter for Instrument Integration factory
>
Specifications
Humidity Tolerance:
±3%RH
Temperature Range:
-40℃~+120℃
Humidity:
0%RH~100%RH
Temperature Tolerance:
±0.2℃
Mfr. Part #:
CHT-DS-I
Key Attributes
Model Number: CHT-DS-I
Product Description

CHT-DS Series Duct Temperature and Humidity Transmitter

The CHT-DS series duct temperature and humidity transmitter utilizes imported digital temperature and humidity sensors, pre-calibrated during production with calibration data stored internally. Featuring digital output for both relative humidity and temperature, these transmitters offer excellent interchangeability without complex calibration. They excel in measurement accuracy, linearity, repeatability, interchangeability, and consistency, making them suitable for environmental equipment, instrument integration, and general environmental testing.

Product Features

  • High cost-performance with wide voltage design.
  • Digital linearization correction for high accuracy and stability.
  • Full-range temperature and humidity compensation, with wide and selectable measurement ranges.
  • Flexible installation and convenient use.
  • Compact size, lightweight, and vibration resistant.
  • Customizable appearance to meet diverse customer needs.

Application Scenarios

Widely used in building automation, telecom equipment rooms, papermaking, warehousing and logistics, shopping malls, hotels, cinemas, train stations, museums, theaters, agricultural greenhouses, hospitals, meteorology, clean workshops, and other fields requiring air temperature and humidity measurement.

Product Attributes

  • Brand: CYBERSEN
  • Origin: Guangzhou CYSEN Technology Co., Ltd.

Technical Specifications

Parameter Specification
Temperature Range Standard: -40~80; Other ranges customizable
Humidity Range 0~100%RH (non-condensing)
Accuracy 0.2 (@25); 3%RH (10%~90%)
Repeatability 0.1; 0.1%RH
Long-term Stability <0.04/year; <0.5%RH/year
Output Signal V: Voltage signal (0-2V, 0-5V, 0-10V selectable); I: 4-20mA (current loop); R: RS485 (Modbus-RTU protocol, default address: 01)
Power Supply Voltage 10~30V DC
Response Time <1S
Operating Environment Temperature: -40~120; Humidity: 95%RH
Load Capacity Voltage output: Output resistance 250; Current output: 600

Data Conversion Methods

Temperature Conversion (for -30~70):
0-2V DC: T = 50*V - 30
0-5V DC: T = 20*V - 30
0-10V DC: T = 10*V - 30
4-20mA: T = 6.25*A - 55

Humidity Conversion:
0-2V DC: H = 50*V
0-5V DC: H = 20*V
0-10V DC: H = 10*V
4-20mA: H = 6.25*A - 25

RS485: Standard Modbus-RTU protocol, Baud rate: 4800; Parity: None; Data bits: 8; Stop bits: 1.

Important Notes

  • Inspect packaging upon receipt and verify product model and specifications.
  • Install away from corrosive environments.
  • Keep sensors and wiring away from high voltage and heat sources.
  • Store sensors in a dry, ventilated, and normal temperature indoor environment.
  • Do not disassemble the sensor to avoid damage.

2402292040_CYBERSEN-CHT-DS-I_C18236194.pdf

Request A Quote

Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible

You Can Upload Up To 5 Files And Each File Sized 10M Max