AN1V PB20 Current Sensor
The AN1V PB20 is an open-loop current sensor based on Hall principle, utilizing ASIC technology for proportional output relative to power supply variations. It offers isolation between primary and secondary sides, has no insertion loss, and comes in a small volume. The sensor is suitable for measuring DC, AC, and pulse currents.
Product Attributes
- Brand: (Chipsensor)
- Primary and secondary sides are insulated
- Raw materials comply with UL 94-V0
- Standards Executed: IEC 60664-1:2020, IEC 61800-5-1:2022, IEC 62109-1:2010
Application Fields
- AC variable frequency drives
- Uninterruptible Power Supply (UPS)
- DC motor driven static converters
- Switch Mode Power Supply (SMPS)
- Welding machine power supplies
- Battery management
- Wind energy converters
Technical Specifications
| Model | Primary Rated Current (RMS) | Primary Current Measurement Range | Supply Voltage (VC) | Zero Point Output Voltage (VQOV) | Theoretical Gain (Gth) | Current Consumption (IC) | Load Resistance (RL) | Output Bandwidth (-3dB) | Accuracy @ IPN X | Tracking Time @ 90% of IPN (tr) |
| (A) | (A) | (V) | (V) | (mV/A) | (mA) | (k) | (kHz) | (% of IPN) | (s) | |
| AN1V 50 PB20 | -50 to 50 | -50 to 50 | 4.5 - 5.5 | VCC/2 | 40 | 8 - 11 | 5.1 | 250 | -2 to 2 | 2.5 - 5 |
| AN1V 100 PB20 | -100 to 100 | -100 to 100 | 4.5 - 5.5 | VCC/2 | 20 | 8 - 11 | 5.1 | 250 | -2 to 2 | 2.5 - 5 |
| AN1V 150 PB20 | -150 to 150 | -150 to 150 | 4.5 - 5.5 | VCC/2 | 13.33 | 8 - 11 | 5.1 | 250 | -2 to 2 | 2.5 - 5 |
| AN1V 200 PB20 | -200 to 200 | -200 to 200 | 4.5 - 5.5 | VCC/2 | 10 | 8 - 11 | 5.1 | 250 | -2 to 2 | 2.5 - 5 |
Environmental and Product Structure Characteristics
| Parameter | Symbol | Unit | Min | Typical | Max | Remarks |
| Operating Temperature | TA | -40 | 150 | AN1V 50 PB20, AN1V 100 PB20 | ||
| Operating Temperature | TA | -40 | 125 | AN1V 150 PB20 | ||
| Operating Temperature | TA | -40 | 85 | AN1V 200 PB20 | ||
| Storage Temperature | TS | -55 | 150 | |||
| Primary Resistance | RP | 100 | ||||
| Mass | g | 5 |
Electrical Characteristics
| Parameter | Symbol | Unit | Value | Remarks |
| AC Isolation Withstand Voltage (RMS @ 50Hz, 1min) | Vd | kV | 4.8 | Refer to IEC 60664-1 |
| Housing Material | UL94-V0 | |||
| Comparative Tracking Index | CTI | PLC | 2 | |
| Application Example (Reinforced Insulation) | 475VRMS | Refer to IEC 61800-5-1, IEC 62109-1 CAT III, PD2 | ||
| Application Example (Basic Insulation) | 960VRMS | Refer to IEC 61800-5-1, IEC 62109-1 CAT III, PD2 |
2408051417_CHIPSENSE-AN1V-50-PB20_C30584738.pdf
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible