CHT-DS Series Duct-Type Temperature and Humidity Transmitter
The CHT-DS series duct-type temperature and humidity transmitter utilizes imported digital temperature and humidity sensors. It features precise pre-calibration with data stored in internal memory. The transmitter offers digital output for both relative humidity and temperature, ensuring interchangeability without complex calibration. It excels in measurement accuracy, linearity, repeatability, interchangeability, and consistency, making it suitable for environmental equipment, instrument integration, and general environmental testing.
Product Features
- High cost-performance ratio with wide voltage design.
- Digital linearization correction for high accuracy and stability.
- Full-range temperature and humidity compensation, wide and selectable measurement range.
- Flexible installation and convenient use.
- Small size, light weight, and vibration resistance.
- Customizable form factors to meet diverse customer needs.
Application Scenarios
Widely used in building automation, telecom equipment rooms, papermaking, warehousing and logistics, shopping malls, hotels, cinemas, train stations, museums, theaters, agricultural greenhouses, hospitals, meteorology, clean workshops, and other fields requiring air temperature and humidity measurement.
Product Attributes
- Brand: CYBERSEN
- Origin: Guangzhou CYSEN Technology Co., Ltd.
- Website: www.cybersen.com
Technical Specifications
| Parameter | Specification |
|---|---|
| Temperature Range | Standard: -40~80; Other ranges can be customized |
| Humidity Range | 0~100%RH (non-condensing) |
| Accuracy | 0.2 (@25); 3%RH (10%~90%) |
| Repeatability | 0.1; 0.1%RH |
| Long-term Stability | <0.04/year; <0.5%RH/year |
| Output Signal | V: Voltage signal (0~2V, 0~5V, 0~10V selectable); I: 4~20mA (current loop); R: RS485 (Modbus-RTU protocol, default address: 01) |
| Power Supply Voltage | 10~30V DC |
| Response Time | <1S |
| Working Environment | Temperature: -40~120; Humidity: 95%RH |
| Load Capacity | Voltage Output: Output resistance 250; Current Output: 600 |
Data Conversion Methods
Temperature Conversion:
- 0~2V DC: T = 50*V - 30
- 0~5V DC: T = 20*V - 30
- 0~10V DC: T = 10*V - 30
- 4~20mA: T = 6.25*A - 55
Humidity Conversion:
- 0~2V DC: H = 50*V
- 0~5V DC: H = 20*V
- 0~10V DC: H = 10*V
- 4~20mA: H = 6.25*A - 25
RS485: Standard Modbus-RTU protocol, Baud Rate: 4800; Parity: None; Data Bits: 8; Stop Bits: 1.
Usage Precautions
- Check packaging for integrity and verify product model and specifications upon receipt.
- Install away from corrosive chemical environments.
- Keep sensors and wires away from high voltage and heat sources.
- Store sensors in a dry, ventilated, and normal temperature indoor environment as they are precision instruments.
- Do not disassemble the sensor yourself to avoid damage.
2310131746_CYBERSEN-CHT-DS-R_C18236193.pdf