Online Service

Online Service

Contact Person
+86 136 6733 2386
quality safe current sensing CHIPSENSE HS1V 100 H03 Hall effect sensor with galvanic separation technology factory
<
quality safe current sensing CHIPSENSE HS1V 100 H03 Hall effect sensor with galvanic separation technology factory
>
Specifications
Mfr. Part #:
HS1V 100 H03
Key Attributes
Model Number: HS1V 100 H03
Product Description

Product Overview

The HS1V H03 SERIES is an open-loop Hall effect current sensor designed for the electronic measurement of DC, AC, and pulsed currents. It provides galvanic separation between the primary and secondary circuits, ensuring safety and reliability. This sensor features a small size, no insertion losses, and an output voltage proportional to the supply voltage, making it suitable for a wide range of industrial applications.

Product Attributes

  • Brand: CHIPSENSE
  • Certifications: UL 94-V0, IEC 60664-1:2020, IEC 61800-5-1:2022, IEC 62109-1:2010

Technical Specifications

Model Number Primary Nominal RMS Current (IPN) Primary Current Measuring Range (IPM) Supply Voltage (VC) Current Consumption (IC) Load Resistance (RL) Output Voltage (VOUT @ IPN) Electrical Offset Voltage (VOE) Temperature Coefficient of VOE (TCVOE) Theoretical Sensitivity (Gth) Sensitivity Error (G) Temperature Coefficient of Sensitivity (TCG) Linearity Error (L) Hysteresis Offset Voltage (VOM) Accuracy @ IPN (X) Response Time (tr @ 90% of IPN) Frequency Bandwidth (-3dB) (BW)
HS1V 50 H03 50 A -150 to 150 A 12 to 15 V 32 mA (typ) 10 k 4.000 V -20 to 20 mV -0.8 to 0.8 mV/K 80.00 mV/A -0.5 to 0.5 % -0.1 to 0.1 %/K -0.5 to 0.5 % of IPN -10 to 10 mV -1 to 1 % of IPN 3 s 50 kHz
HS1V 100 H03 100 A -300 to 300 A 12 to 15 V 32 mA (typ) 10 k 4.000 V -20 to 20 mV -0.8 to 0.8 mV/K 40.00 mV/A -0.5 to 0.5 % -0.1 to 0.1 %/K -0.5 to 0.5 % of IPN -10 to 10 mV -1 to 1 % of IPN 3 s 50 kHz
HS1V 200 H03 200 A -600 to 600 A 12 to 15 V 32 mA (typ) 10 k 4.000 V -20 to 20 mV -0.8 to 0.8 mV/K 20.00 mV/A -0.5 to 0.5 % -0.1 to 0.1 %/K -0.5 to 0.5 % of IPN -10 to 10 mV -1 to 1 % of IPN 3 s 50 kHz
HS1V 300 H03 300 A -900 to 900 A 12 to 15 V 32 mA (typ) 10 k 4.000 V -20 to 20 mV -0.8 to 0.8 mV/K 13.33 mV/A -0.5 to 0.5 % -0.1 to 0.1 %/K -0.5 to 0.5 % of IPN -10 to 10 mV -1 to 1 % of IPN 3 s 50 kHz
HS1V 400 H03 400 A -900 to 900 A 15 V 0.6 mA (@+15V), 0.6 mA (@-15V) 10 k 4.000 V -20 to 20 mV -0.8 to 0.8 mV/K 10.00 mV/A -0.5 to 0.5 % -0.1 to 0.1 %/K -0.5 to 0.5 % of IPN -10 to 10 mV -1 to 1 % of IPN 3 s 50 kHz
HS1V 500 H03 500 A -900 to 900 A 15 V 0.6 mA (@+15V), 0.6 mA (@-15V) 10 k 4.000 V -20 to 20 mV -0.8 to 0.8 mV/K 8.00 mV/A -0.5 to 0.5 % -0.1 to 0.1 %/K -0.5 to 0.5 % of IPN -10 to 10 mV -1 to 1 % of IPN 3 s 50 kHz
HS1V 600 H03 600 A -900 to 900 A 15 V 0.6 mA (@+15V), 0.6 mA (@-15V) 10 k 4.000 V -20 to 20 mV -0.8 to 0.8 mV/K 6.67 mV/A -0.5 to 0.5 % -0.1 to 0.1 %/K -0.5 to 0.5 % of IPN -10 to 10 mV -1 to 1 % of IPN 3 s 50 kHz

Applications

  • AC variable speed
  • Uninterruptible Power Supply (UPS)
  • Static converters for DC motor drives
  • Switch Mode Power Supplies (SMPS)
  • Power supplies for welding applications
  • Battery management
  • Wind energy inverter

Safety and Usage

This sensor must be used in accordance with IEC61800-5-1 and applicable standards and safety requirements. Caution: risk of electrical shock. Hazardous voltages may be present on certain parts of the module during operation. This sensor is a built-in device, and its conducting parts must be inaccessible after installation. A protective housing or additional shield may be required. The main supply must be disconnectable.

Environmental and Mechanical Characteristics

Parameter Symbol Unit Min Typ Max Comment
Ambient operating temperature TA -40 105
Ambient storage temperature TS -40 105
Mass m g 57

Insulation Coordination

Parameter Symbol Unit Value Comment
Rms voltage for AC insulation test @ 50Hz,1min Vd kV 3.6
Impulse withstand voltage 1.2/50s VW kV 6.6
Clearance (pri.- sec.) dCI mm 6.3 According to IEC 60664-1
Creepage distance (pri.- sec.) dCp mm 7.3 According to IEC 60664-1
Plastic case - - UL94-V0
Comparative tracking index CTI PLC 3
Application example - - 300V Reinforced insulation, according to IEC 61800-5-1, IEC 62109-1 CAT III, PD2
Application example - - 600V Basic insulation, according to IEC 61800-5-1, IEC 62109-1 CAT III, PD2

Dimensions

Dimensions in mm.

Characteristic Specification
General tolerance 0.5 mm
Connection of secondary RVV4*0.2mm
Output line length 50010mm
Primary hole 20.4mm10.4mm
Sensor Recommended fastening torque 1pc 4.5 mm through hole, 1pc M4 Metal screws, 0.9 Nm (10%)

Remarks

  • vOUT and IP are in the same direction when IP flows in the direction of the arrow.
  • Temperature of the primary conductor should not exceed 105.
  • Dynamic performances (di/dt and response time) are best with a single bar completely filling the primary hole.