Product Overview
The Wireless Communication Concentrator is designed for efficient data collection in industrial environments. It comprises a central host (concentrator) and multiple subordinate devices (slaves) that communicate wirelessly. The host unit collects data from all connected slave devices and forwards it to an upper-level system, such as a gateway or PC, via RS485 or RS232 (TTL) interface. This system is ideal for scenarios requiring centralized data acquisition from distributed wireless sensors and devices.
Product Attributes
- Brand: Beijing Huoyuan Technology Co., Ltd.
- Default Antenna Type: Suction cup antenna
- Optional Antenna Type: Rod antenna (specify when ordering)
Technical Specifications
| Specification | Details |
|---|---|
| Concentrator Auxiliary Power | Switching Power Supply: AC110V245V; Linear Power Supply: 220Vac10% |
| Communication Interface | RS485 or RS232 (TTL) |
| Baud Rate | 2400bps, 4800bps, 9600bps (Default: 9600bps) |
| Wireless Parameters | Wireless Power: 14dbm; Operating Frequency Band: 433MHz |
| Transmission Distance | Up to 200 meters in open space |
| Max. Slave Devices per Concentrator | 200 units |
| Safety (Power Frequency Withstand Voltage) | RS485 Interface to Auxiliary Power: AC2KV 1min |
| Environmental Operating Temperature | -30 to +70 |
| Environmental Storage Temperature | -10 to +70 |
| Environmental Relative Humidity | 5%95% (non-condensing) |
| Environmental Altitude | 2000m |
| Concentrator Dimensions | Refer to diagram (L, N for AC220V power; A, B for RS485) |
| Host Module Power Supply Options | 3.3V or 5V |
| Communication Protocol (Host to Upper Device) | Standard MODBUS-RTU Protocol |
| Host Default Address | 0xFE (254) |
| Slave Data Storage | Each slave occupies 30 registers for real-time data. |
| Slave Register Address Calculation | (Slave ID - 1) * 30 + 201 = Starting Register Address |
| Slave ID Range | 1 to 200 |
| Slave Register Data Items (Examples) | Chip Unique Identifier (IEEE Address Low 16-bit), Receive Timeout, Online Status, Cable Vibration Status, Cable Current Value, Cable Temperature Value, CT Opening Status, Cable Live Status, Slave Reset Command, Harmonic Order, Harmonic Amplitude. (Items marked with * are optional functions) |
Communication Indicator Lights
| Indicator Name | Normal Status | Off Status | Remarks |
|---|---|---|---|
| Power Light | Constantly on | No power | Normally on |
| Communication Light | Flashing | No data communication | Off when no communication or connection |
| Wireless Light | Flashing once | No communication | Off when no communication or RF signal is not bright |
2412231549_Beijing-Hop-Tech-HLW-M-W_C2880429.pdf