Product Overview
The HCT632S-18EMI is a residual current sensor designed for detecting various leakage current waveforms. It integrates a detection circuit and a micro-processing unit, offering low power consumption, high accuracy, good linearity, strong anti-interference capabilities, minimal temperature drift, and isolated current detection. This sensor features a compact design, direct output of tripping levels, precise action thresholds, resistance to strong magnetic fields (up to 30mT), robust EMC performance, intelligent computation, and fast response times. It is suitable for 120V, 250V, and 380V power systems, applicable to both single-phase and three-phase configurations. The product meets IEC 62752 Mode II IC-CPD and IEC 62955 Mode III RDC-DD charging-related residual current test requirements, and is compatible with DC6mA test demands. It is ideal for isolated DC and AC leakage current detection and serves as a dedicated A+6 type residual current protection module for charging piles.
Product Attributes
- Brand: HOP ()
Technical Specifications
| Parameter | Specification | Unit | Notes |
|---|---|---|---|
| Product Model | HCT632S-18EMI | - | Residual Current Sensor |
| Residual Current Parameters - Action Current | Waveform: DC_SM | mA | National Standard Range: 3 - 6.0; Sensor Actual: 4.0 (Min) - 5.2 (Typ) - 6.0 (Max) |
| Waveform: AC 50Hz | mA | National Standard Range: 15 - 30; Sensor Actual: 20.0 (Min) - 26 (Typ) - 30.0 (Max) | |
| Waveform: A0 50Hz | mA | National Standard Range: 4.5 - 42; Sensor Actual: 20 (Min) - 28 (Typ) - 42.0 (Max) | |
| Waveform: A90 50Hz | mA | National Standard Range: 6.3 - 42; Sensor Actual: 20 (Min) - 28 (Typ) - 42.0 (Max) | |
| Waveform: A135 50Hz | mA | National Standard Range: 3.3 - 42; Sensor Actual: 20 (Min) - 30 (Typ) - 42.0 (Max) | |
| Waveform: (2PDC) | mA | National Standard Range: 3 - 7.0; Sensor Actual: 4.0 (Min) - 6.0 (Typ) - 7.0 (Max) | |
| Waveform: (3PDC) | mA | National Standard Range: 3.1 - 6.2; Sensor Actual: 4.0 (Min) - 5.2 (Typ) - 6.2 (Max) | |
| Waveform: IC_CPD | mA | National Standard Range: 15 - 42; Sensor Actual: 26 (Min) - 36.0 (Typ) - 42.0 (Max) | |
| Waveform: F Composite Wave 1kHz | mA | National Standard Range: 15 - 42; Sensor Actual: 26 (Min) - 36.0 (Typ) - 42.0 (Max) | |
| Supply Voltage (VDD) | 5 5% | Vdc | VDD ripple requirement <30mV. VDD fluctuation within 5%. |
| Static Power Consumption | < 10 | mA | |
| Static Power Consumption | 50 | mW | |
| Power Supply Output Capability | > 200 | mA | |
| Voltage Output Low Level | 0 0.6 | Vdc | |
| Voltage Output High Level | VDD 20% | Vdc | |
| Power Frequency Withstand Voltage (Input to Output) | 4000 | V/60s | When input is enameled wire or cable with insulation sheath. |
| Operating Temperature | -40 to +85 | ||
| Storage Temperature | -40 to +105 | ||
| Temperature Rise | 25 | K | |
| External Magnetic Field Resistance | 30 | mT | Tested on outer casing arc surface. |
| AC Power Line Current Test | 1500 | A | External AC power cable attached to the side wall of the sensor. |
| Pin Description: TRIP | Output | - | Outputs high level when residual current exceeds threshold, otherwise low. Requires external 1k current limiting resistor (drive capability 5mA). |
| Pin Description: ERROR | Output | - | Outputs high level when system error occurs, otherwise low. Requires external 1k current limiting resistor (drive capability 5mA). |
| Pin Description: CLR&CHK | Input | - | Clear & Self-check pin (short to ground for 0.6-1.2s to trigger). Recommended system working level conversion circuit. |
| Pin Description: GND | Input | - | Module Ground. |
| Pin Description: VDD | Input | Vdc | Power supply 5Vdc0.25Vdc. |
| Pin Description: NC | N/A | - | No Connection. |
Application Fields
- Isolated DC and AC leakage current detection
- Dedicated A+6 type residual current protection module for charging piles
2508221710_Beijing-Hop-Tech-HCT632S-18EMI_C5375347.pdf
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible