Product Overview
The Telaire 8000 Ventostat series offers wall-mount CO2, humidity, and temperature transmitters designed for controlled ventilation in commercial HVAC applications. These devices help maintain indoor air quality, prevent energy waste from over-ventilation, and are ideal for areas with fluctuating occupancy. Featuring a patented Absorption Infrared Gas sensing engine and ABC Logic self-calibration system, they provide high accuracy and eliminate the need for manual calibration in most applications, backed by a lifetime CO2 calibration guarantee for T8100 and T8300 models. The two-piece design allows for easy replacement without rewiring, and modern enclosures with customizable branding are available. Suitable for controlling specific areas like conference rooms, classrooms, and meeting halls.
Product Attributes
- Brand: Telaire (Amphenol Advanced Sensors)
- Series: Ventostat 8000
- Sensing Technology: Patented Absorption Infrared Gas sensing engine
- Self-Calibration: Patented ABC Logic
- Calibration Guarantee: Lifetime for T8100/T8300 (single channel), 2-year for T8200 (dual channel)
- Enclosure: Modern design, customizable branding available. Smaller enclosure versions available (81.4 mm x 86.4 mm).
- Certifications: CE and RoHS compliant
- Design: Two-piece design for easy replacement
- Filter: Gas permeable, water resistant CO2 diffusion filter
- Output Options: Dual simultaneous analog (V & mA), BACnet (MS/TP, RS485)
- Origin: Controlled Ventilation
Technical Specifications
| Specification | Details |
|---|---|
| Models | T8100 (Single Channel, ABC Logic), T8200 (Dual Channel), T8300 (Single Channel with Pitot Tube Kit) |
| CO2 Measurement Range | 0 to 2000 ppm (Standard) 0 to 5000 ppm (T8100/T8200/T8300 -5P models) 0 to 10,000 ppm (T8200 - 10P models) 0 to 20,000 ppm (T8200 - 20P models) |
| CO2 Accuracy | 30ppm or 3% of reading, whichever is higher (excludes calibration gas and DA error) |
| Power Supply Requirements | 18-30 VAC RMS, 50/60 Hz, or 10.8 to 42 VDC, polarity protected |
| Power Consumption | Typical 0.7 W at 24V AC RMS |
| Temperature Dependence | 0.2% FS per C (0.11% per F) |
| Stability | T8100/T8300: <2% of FS over life (15 years) T8200: <5% of FS or <10% reading annual over life (10 years) |
| Pressure Dependence | 0.135% of reading per mm Hg |
| Warranty | 24 months on mechanical defects |
| Signal Update | Every 5 seconds |
| CO2 Warm-up Time | < 2 minutes (operational), 10 minutes (maximum accuracy) |
| Operating Conditions | 32F to 122F (0C to 50C), 0 to 95% RH (non-condensing) |
| Storage Conditions | -40F to 158F (-40C to 70C) |
| Flammability Classification | UL94 5VA |
| Thermistor Type | NTC 10 K W (Passive, not BACnet version) |
| Thermistor Accuracy | 1C (15 to 35C) |
| RH Sensing Element | Capacitive polymer sensor |
| RH Range | 0% to 99% RH (non-condensing) |
| RH Accuracy (25C) | 2.5% RH (20 to 80% RH), 3.5% RH (<20% and >80% RH) |
| Active Temperature Accuracy | 0.8C @ 22C |
| Active Temperature Range | 32F to 122F (0 to 50C) |
| Analog Output | 0 to 10 V (100 W impedance) and 4 to 20mA (RL max 500 W) simultaneously |
| BACnet Version | MS/TP, RS485, Baud rates 38400 or 9600 |
| T8300 Pitot Tube Kit | For duct measurement of CO2 |
| Field Replaceable RH Sensor Tip | Maintains 2.5% RH accuracy |
| Accessories | T1505 Splash Resistant Enclosure, T1552 Outside Air Enclosure, T1508 Aspiration Box for Duct Mounting |
| UIP Software (T2090) | Altitude adjustment, analog output adjustment, calibration, ABC Logic control, temperature unit change, graphing/logging |
2411041546_Amphenol-T8100-D-GN-R_C17542925.pdf
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible