Product Overview
Telaire Ventostat 8000 series wall mount transmitters are designed for monitoring CO2, humidity, and temperature in building HVAC applications. These devices are crucial for demand-controlled ventilation, preventing energy waste from over-ventilation while maintaining optimal indoor air quality. They are ideal for controlling specific areas such as conference rooms, classrooms, and meeting halls. Key features include patented Absorption Infrared Gas sensing engines, ABC Logic self-calibration for most applications, and a two-piece design for easy replacement without rewiring. Available in various configurations, including models with displays and BACnet output, these transmitters offer dual simultaneous analog outputs (V & mA) for CO2 and include a temperature sensor on all models.
Product Attributes
- Brand: Telaire, Amphenol Advanced Sensors
- Series: Ventostat 8000
- Sensing Technology: Patented Absorption Infrared Gas sensing engine (NDIR)
- Calibration System: Patented ABC Logic self-calibration (T8100, T8300), Dual-channel self-calibration (T8200)
- Calibration Guarantee: Lifetime for T8100/T8300 with ABC Logic, 2 years for T8200
- Enclosure Options: Standard, smaller enclosures, Splash Resistant (T1505), Outside Air (T1552), Aspiration Box for Duct Mounting (T1508)
- Certifications: CE and RoHS compliant
- Customization: Customized branding available
- Design: Modern enclosure, Two-piece design for easy replacement
- Filter: Gas permeable, water resistant CO2 diffusion filter
- Output Options: Dual simultaneous analog outputs (0-10V & 4-20mA), BACnet MS/TP (RS485)
- Origin: Controlled Ventilation
Technical Specifications
| Specification | Details |
|---|---|
| Models | T8100, T8200, T8300 |
| CO2 Measurement Range (Standard) | 0 to 2000 ppm |
| CO2 Measurement Range (T8100/T8200/T8300 -5P models) | 0 to 5000 ppm |
| CO2 Measurement Range (T8200 - 10P models) | 0 to 10,000 ppm |
| CO2 Measurement Range (T8200 - 20P models) | 0 to 20,000 ppm |
| CO2 Accuracy | 30 ppm or 3% of reading, whichever is higher |
| CO2 Sensing Method | Non-dispersive infrared (NDIR) absorption, Gold-plated optics |
| CO2 Warm-up Time | < 2 minutes (operational), 10 minutes (maximum accuracy) |
| Temperature Sensor Type | Passive Thermistor (NTC 10 K W) on non-BACnet versions |
| Active Temperature Range | 32F to 122F (0C to 50C) |
| Active Temperature Accuracy | 0.8C @ 22C |
| RH Sensing Element | Capacitive polymer sensor |
| RH Range | 0% to 99% RH (non-condensing) |
| RH Accuracy (25C) | 2.5% RH (20 to 80% RH), 3.5% RH (<20% and >80% RH) |
| Power Supply Requirements | 18-30 VAC RMS, 50/60 Hz, or 10.8 to 42 VDC, polarity protected |
| Power Consumption | Typical 0.7 W at 24V AC RMS |
| Operating Conditions | 32F to 122F (0C to 50C), 0 to 95% RH (non-condensing) |
| Storage Conditions | -40F to 158F (-40C to 70C) |
| Flammability Classification | UL94 5VA |
| Warranty | 24 months on mechanical defects |
| Signal Update | Every 5 seconds |
| Analog Output (Standard) | 0 to 10 V (100 output impedance) and 4 to 20mA (RL max 500 ) available simultaneously |
| BACnet Version | MS/TP, RS485, Baud rates 38400 or 9600 |
| T8300 Pitot Tube Kit | For duct measurement of CO2 |
| Field-Replaceable Sensor Tip | Relative Humidity (RH) sensor tip module |
| UIP Software Features | Altitude adjustment, Analog output adjustment, Calibration, ABC Logic control, Temperature unit change, Graphing/logging (H versions) |
| T1505 Enclosure | Splash Resistant, ABS plastic, for damp/wet environments, slows response time to ~30 mins for 90% step change |
| T1552 Enclosure | Outside Air, weatherproof ABS plastic, temperature control circuit and heaters, slows response time to ~30 mins for 90% step change |
| T1508 Enclosure | Aspiration Box for Duct Mounting, ABS plastic, for flow rates > 400 fpm, accommodates Ventostat 8100/8200 series |
2504101957_Amphenol-T8100-HD_C17375855.pdf