Product Overview
The Telaire 8000 Ventostat series offers reliable wall-mount CO2, humidity, and temperature transmitters designed for controlled ventilation in commercial HVAC applications. These transmitters help maintain optimal indoor air quality, enhance occupant health and productivity, and prevent energy waste from over-ventilation. Featuring patented sensing technology and self-calibration systems, they minimize maintenance requirements. The two-piece design facilitates easy installation and replacement without rewiring. Available in various configurations, including models with displays and BACnet output, the Ventostat 8000 series is suitable for controlling specific areas like conference rooms, classrooms, and meeting halls.
Product Attributes
- Brand: Telaire (Amphenol Advanced Sensors)
- Series: Ventostat 8000
- Certifications: CE and RoHS compliant
- Enclosure Options: Standard, smaller enclosures (black/white), splash-resistant (T1505), outside air (T1552), aspiration box for duct mounting (T1508)
- Customization: Modern enclosure with customized branding available
Technical Specifications
| Specification | Details |
|---|---|
| Sensing Method | Non-dispersive infrared (NDIR) absorption; Patented ABC Logic self-calibration algorithm; Gold-plated optics |
| CO2 Measurement Range | T8100/T8200/T8300: 0 to 2000 ppm T8100/T8200/T8300 - 5P models: 0 to 5000 ppm T8200 (10P models): 0 to 10,000 ppm T8200 (20P models): 0 to 20,000 ppm |
| CO2 Accuracy | 30ppm or 3% of the reading shown, whichever is higher* |
| Temperature Sensor | Passive Thermistor (NTC 10 K W) or Active Temperature Sensor Accuracy: 1C (15 to 35C) for thermistor; 0.8C @ 22C for active Range: 32F to 122F (0C to 50C) |
| Humidity Sensor | Capacitive polymer sensor Range: 0% to 99% RH (non-condensing) Accuracy (25C): 2.5% RH (20 to 80% RH); 3.5% RH (<20% and >80% RH) |
| Power Supply Requirements | 18-30 VAC RMS, 50/60 Hz, or 10.8 to 42 VDC, polarity protected |
| Power Consumption | Typical 0.7 W at nominal voltage of 24V AC RMS |
| Operating Conditions | 32F to 122F (0C to 50C); 0 to 95% RH, non-condensing |
| Storage Conditions | -40F to 158F (-40C to 70C) |
| Signal Update | Every 5 seconds |
| CO2 Warm-up Time | < 2 minutes (operational); 10 minutes (maximum accuracy) |
| Output Options | Analog: Dual simultaneous 0-10 V and 4-20mA BACnet: MS/TP, RS485 (38400 or 9600 baud) |
| Warranty | 24 months on mechanical defects; Lifetime calibration guarantee for T8100/T8300 (ABC Logic enabled); 2-year calibration guarantee for T8200 |
| Models | T8100: Single channel, ABC Logic, lifetime calibration T8200: Dual channel, enhanced stability/accuracy, annual calibration recommended T8300: Single channel with pitot tube kit for duct measuring, ABC Logic |
| Dimensions | Standard: 81.4 mm x 86.4 mm (smaller enclosures) |
| Field Serviceability | Field-replaceable RH sensor tip module |
*CO2 accuracy statement excludes standard gas used for calibration that has an accuracy of 2%. In addition, there is a potential digital to analog error of up to 1%.
2411041546_Amphenol-T8200-GN_C7604366.pdf
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible