Product Overview
The Telaire 8000 Ventostat series offers wall-mount CO2, humidity, and temperature transmitters designed for controlled ventilation in commercial HVAC applications. These transmitters help maintain indoor air quality, optimize energy efficiency by preventing over-ventilation, and ensure a healthy, productive environment. Featuring advanced sensing technology like patented Absorption Infrared Gas sensing and ABC Logic self-calibration, they provide high accuracy and minimize maintenance. The two-piece design facilitates easy installation and replacement without rewiring. Available in various configurations, including models with displays and BACnet output, the Ventostat 8000 series is suitable for controlling specific areas such as conference rooms, classrooms, and meeting halls.
Product Attributes
- Brand: Telaire, Amphenol Advanced Sensors
- Series: Ventostat 8000
- Sensing Technology: Patented Absorption Infrared Gas sensing engine, Patented ABC Logic self-calibration system
- Outputs: Dual simultaneous analog outputs (0-10 V & 4-20mA), BACnet MS/TP (RS485)
- Calibration: Factory calibrated, Lifetime CO2 calibration guarantee (T8100/T8300 with ABC Logic), Annual calibration recommended (T8200)
- Design: Modern enclosure, Two-piece design, Mounting plate with two-piece terminal blocks, Gas permeable water resistant CO2 diffusion filter, Locking screw for tamper resistance
- Field Serviceability: Field-replaceable RH sensor tip module
- Certifications: CE, RoHS compliant
- Optional features: Display, Humidity sensor, Pitot tube kit for duct measurement, Splash resistant enclosure (T1505), Outside air enclosure (T1552), Aspiration box for duct mounting (T1508)
- Enclosure Colors: Black (B), White (W) available
Technical Specifications
| Specification | Details |
|---|---|
| CO2 Measurement Range | 0 to 2000 ppm (Standard) 0 to 5000 ppm (T8100/T8200/T8300 -5P models) 0 to 10,000 ppm (T8200 -10P models) 0 to 20,000 ppm (T8200 -20P models) |
| CO2 Accuracy | 30 ppm or 3% of reading, whichever is higher |
| Power Supply | 18-30 VAC RMS, 50/60 Hz, or 10.8 to 42 VDC, polarity protected |
| Power Consumption | Typical 0.7 W at 24V AC RMS |
| Temperature Dependence | 0.2% FS per C |
| Stability | T8100/T8300: <2% of FS over life (15 years) T8200: <5% of FS or <10% reading annual over life (10 years) |
| Pressure Dependence | 0.135% of reading per mm Hg |
| Warranty | 24 months on mechanical defects |
| Signal Update | Every 5 seconds |
| CO2 Warm-up Time | < 2 minutes (operational) 10 minutes (maximum accuracy) |
| Operating Conditions | 32F to 122F (0C to 50C) 0 to 95% RH, non-condensing |
| Storage Conditions | -40F to 158F (-40C to 70C) |
| Flammability Classification | UL94 5VA |
| Thermistor Type | NTC 10 K W (Passive, not BACnet version) |
| Thermistor Accuracy | 1C (15 to 35C) |
| RH Sensing Element | Capacitive polymer sensor |
| RH Range | 0% to 99% RH (non-condensing) |
| RH Accuracy (25C) | 2.5% RH (20 to 80% RH) 3.5% RH (<20% and >80% RH) |
| Active Temperature Accuracy | 0.8C @ 22C |
| Active Temperature Range | 32F to 122F (0 to 50C) |
| Analog Output Impedance | 10 V (100 W) 4-20mA (RL maximum 500 W) |
| BACnet Baud Rates | 38400 or 9600 |
| Model T8100 | Single channel sensor, ABC Logic enabled |
| Model T8200 | Dual channel optical system, three-point calibration |
| Model T8300 | Single channel sensor with pitot tube kit for duct measuring, ABC Logic enabled |
| Dimensions (Smaller Enclosures) | 81.4 mm x 86.4 mm |
| T1505 Enclosure Response Time | Approx. 30 minutes for 90% step change |
| T1552 Enclosure Temperature Range | Down to -20F (-29C) |
| T1552 Power Consumption | 24V, 1.5 Amp (max) |
| T1508 Probe Dimensions | 1-inch (25.4mm) diameter x 8-inch (203.2mm) long |
2411041546_Amphenol-T8200-E-D-5P-R_C17376602.pdf
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible