Product Overview
The Telaire Wall Mount CO2, Humidity, and Temperature Transmitters, part of the Ventostat 8000 series, are designed for controlled ventilation in buildings. They help maintain indoor air quality, occupant health, and productivity while preventing energy waste from over-ventilation. These transmitters are ideal for demand-controlled ventilation strategies, particularly in buildings with fluctuating occupancy. They are suitable for controlling specific areas like conference rooms, classrooms, and meeting halls. The two-piece design allows for easy replacement without rewiring, and modern enclosures can be customized with branding. Available in various configurations, including models with dual analog outputs (V & mA) and BACnet output versions, these sensors are factory calibrated and feature a lifetime CO2 calibration guarantee when using ABC Logic.
Product Attributes
- Brand: Telaire, Amphenol Advanced Sensors
- Series: Ventostat 8000
- Sensing Technology: Patented, Absorption Infrared Gas sensing engine (NDIR)
- Calibration System: Patented ABC Logic self-calibration (T8100, T8300), Dual-channel self-calibration (T8200)
- Calibration Guarantee: Lifetime for T8100/T8300 with ABC Logic; 24 months on mechanical defects for all models.
- Certifications: CE, RoHS compliant
- Enclosure Options: Standard, Smaller Enclosures (81.4 mm x 86.4 mm), Splash Resistant (T1505), Outside Air (T1552), Aspiration Box for Duct Mounting (T1508)
- Field Serviceability: Field-replaceable Relative Humidity (RH) sensor tip module
Technical Specifications
| Specification | Details |
|---|---|
| CO2 Measurement Range | T8100/T8200/T8300: 0 to 2000 ppm T8100/T8200/T8300 - 5P models: 0 to 5000 ppm T8200 (10P models): 0 to 10,000 ppm T8200 (20P models): 0 to 20,000 ppm |
| CO2 Accuracy | 30 ppm or 3% of the reading shown, whichever is higher* |
| Power Supply Requirements | 18-30 VAC RMS, 50/60 Hz, or 10.8 to 42 VDC, polarity protected |
| Power Consumption | Typical 0.7 W at nominal voltage of 24V AC RMS |
| Temperature Dependence | 0.2% FS per C (0.11% per F) |
| Stability | T8100/T8300 - Single Channel: <2% of FS over life of sensor (15 years) T8200 - Dual Channel: <5% of FS or <10% reading annual over life of sensor (10 years) |
| Pressure Dependence | 0.135% of reading per mm Hg |
| Warranty | 24 months on mechanical defects |
| Signal Update | Every 5 seconds |
| CO2 Warm-up Time | < 2 minutes (operational) 10 minutes (maximum accuracy) |
| Operating Conditions | 32F to 122F (0C to 50C) 0 to 95% RH, non-condensing |
| Storage Conditions | -40F to 158F (-40C to 70C) |
| Flammability Classification | UL94 5VA |
| Passive Thermistor Type | NTC 10 K W thermistor (not BACnet version) |
| Thermistor Accuracy | 1C (15 to 35C) |
| RH Sensing Element | Capacitive polymer sensor |
| RH Range | 0% to 99% RH (non-condensing) |
| RH Accuracy (25C) | 2.5% RH (20 to 80% RH) 3.5% RH (<20% and >80% RH) |
| Active Temperature Accuracy | 0.8C @ 22C |
| Active Temperature Range | 32F to 122F (0 to 50C) |
| Analog Output Version | 0 to 10 V (100 W output impedance) and 4 to 20mA (RL maximum 500 W) available simultaneously |
| BACnet Version | MS/TP, RS485, Baud rates 38400 or 9600 |
| Models | T8100 (Single channel, ABC Logic) T8200 (Dual channel, enhanced stability) T8300 (Single channel with pitot tube kit for duct measuring, ABC Logic) |
2411041546_Amphenol-T8300-B-GN_C17539610.pdf
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible