Specifications
Mfr. Part #:
T8100-E-D-R
Key Attributes
Model Number:
T8100-E-D-R
Product Description
Product Overview
The Telaire 8000 Ventostat series offers wall-mount CO2, humidity, and temperature transmitters designed for controlled ventilation in commercial HVAC applications. These transmitters help maintain indoor air quality, prevent energy waste from over-ventilation, and support demand-controlled ventilation strategies. Featuring patented sensor technology like Absorption Infrared Gas sensing and ABC Logic self-calibration, they provide high accuracy and reduce maintenance needs. The two-piece design facilitates easy installation and replacement without rewiring. Available in various configurations, including models with displays and BACnet output, they are suitable for controlling specific areas such as conference rooms, classrooms, and meeting halls.Product Attributes
- Brand: Telaire, Amphenol Advanced Sensors
- Product Series: Ventostat 8000
- Sensing Technology: Patented Absorption Infrared Gas sensing engine, Patented ABC Logic self-calibration system
- Calibration Guarantee: Lifetime CO2 calibration guarantee (T8100/T8300 with ABC Logic), 2-year calibration guarantee (T8200)
- Enclosure Design: Modern enclosure, Two-piece design, Customized branding available, Smaller enclosure versions available (81.4 mm x 86.4 mm)
- Certifications: CE and RoHS compliant
- Intended Use: Occupied building HVAC applications
- Not Designed For: Safety critical functions
- Optional Accessories: T1505 Splash Resistant Enclosure, T1552 Outside Air Enclosure, T1508 Aspiration Box for Duct Mounting
- Software: Ventostat UIP Software for configuration and calibration
Technical Specifications
| Specification | Details |
|---|---|
| Models | T8100 (Single Channel, ABC Logic), T8200 (Dual Channel), T8300 (Single Channel with Pitot Tube Kit) |
| CO2 Measurement Range | 0 to 2000 ppm (Standard) 0 to 5000 ppm (T8100/T8200/T8300 -5P models) 0 to 10,000 ppm (T8200 - 10P models) 0 to 20,000 ppm (T8200 - 20P models) |
| CO2 Accuracy | 30ppm or 3% of reading, whichever is higher* |
| CO2 Sensing Method | Non-dispersive infrared (NDIR) absorption, Gold-plated optics |
| CO2 Diffusion Filter | Gas permeable, water resistant |
| Temperature Sensor Type | Passive Thermistor (NTC 10 K W) on non-BACnet versions |
| Temperature Accuracy | 1C (15 to 35C) for Thermistor 0.8C @ 22C for Active Temperature |
| Temperature Operating Range | 32F to 122F (0C to 50C) |
| RH Sensing Element | Capacitive polymer sensor |
| RH Range | 0% to 99% RH (non-condensing) |
| RH Accuracy (25C) | 2.5% RH (20 to 80% RH) 3.5% RH (<20% and >80% RH) |
| Power Supply Requirements | 18-30 VAC RMS, 50/60 Hz, or 10.8 to 42 VDC, polarity protected |
| Power Consumption | Typical 0.7 W at 24V AC RMS |
| Signal Update Rate | Every 5 seconds |
| CO2 Warm-up Time | < 2 minutes (operational), 10 minutes (maximum accuracy) |
| Operating Conditions | 32F to 122F (0C to 50C), 0 to 95% RH (non-condensing) |
| Storage Conditions | -40F to 158F (-40C to 70C) |
| Flammability Classification | UL94 5VA |
| Warranty | 24 months on mechanical defects |
| Output Options | Analog: Dual simultaneous 0-10 V and 4-20 mA BACnet: MS/TP, RS485 (38400 or 9600 baud rates) |
| Field Serviceability | Field-replaceable RH sensor tip module |
| T8300 Pitot Tube Kit | For duct measurement of CO2 |
| T1508 Aspiration Box | For in-duct sampling (>400 fpm), accommodates 8100/8200 series |
*CO2 accuracy statement excludes standard gas used for calibration (accuracy of 2%) and potential digital to analog error (up to 1%).
2411041546_Amphenol-T8100-E-D-R_C17641088.pdf
Request A Quote
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible