Product Overview
The Amphenol Advanced Sensors Telaire T3030 Series CO2 Sensors are designed for accurate CO2 measurement in harsh or difficult environments, offering reliable performance for HVAC control applications. These sensors feature a Non-Dispersive Infrared (NDIR) measuring technology and are available with analog or digital output options. With easy mounting via external tabs and an IP67 rating (build dependent), the T3030 series is suitable for demanding applications such as incubators, buses, refrigerators, subway stations, railway carriages, and agricultural settings like glass houses and animal sheds. The sensors are factory-calibrated and offer a 10-year life accuracy with an extended operating temperature range.
Product Attributes
- Brand: Amphenol Advanced Sensors Telaire
- Sensing Method: Non-Dispersive Infrared (NDIR), single or dual wavelength
- Calibration Guarantee: Lifetime for single wavelength, 2 years for dual wavelength
- Flammability Classification: To UL94 5VA (dependent upon build)
- Output Options: Analog (0-5 V, 0-10 V, 4-20mA), Digital (Modbus, UART)
- Measuring Technology Options: Single Wavelength with ABC Logic, Dual Wavelength
- Ingress Protection: Up to IP67 (dust tight and immersion to 1m)
- Potting: Optional
Technical Specifications
| Specification | Details |
|---|---|
| Product Series | T3030 Series |
| Power Supply Requirements | 15 15 VDC 10%, 24 - 18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected |
| Power Consumption | Typical 0.7 W at nominal voltage of 24V AC RMS |
| Resolution | Minimum 10bit or analog equivalent |
| Accuracy (Single Wavelength, 0~2,000 ppm example) | 400-1250 ppm 30 ppm or 3% of reading (whichever is greater); 1250-2000 ppm 5% of reading + 30ppm |
| Accuracy (Dual Wavelength, 0~2,000 ppm example) | 75 ppm or 10% of reading (whichever is greater) |
| Accuracy (Dual Wavelength, 0~200,000 ppm example) | 5% of reading or 0.3 vol% CO2 (whichever is larger) at 0 - 20 vol% CO2 and 0C to +25C; At 25C to 50C additional 0.1% of reading or 0.01 vol% CO2 (whichever is larger) per degree C. |
| Temperature Dependence | 0.2% FS / C |
| Response Time (tau 63%) | < 200 sec |
| Aging (Dual Wavelength Only) | +/- 5% of reading annual drift. Less than +/- 25% of reading within product life time. |
| Recommended Recalibration Interval | Single Wavelength No calibration required; Dual Wavelength - 1 year |
| Working Temperature | 0 to +50C (measures within tolerance) |
| Operation Temperature (Sensor Is Powered) | -30 to +50C |
| Storage Temperature | -40 to +70C |
| Minimum Lifetime | 10 years or 30,000 operating hours |
| RH Range | 0% to 99% RH (non-condensing) |
| Atmospheric Conditions Tested | Marine, salt mist and particles present; O2 level 0-21 vol%; 0 to 100% RH; Ammonium max 200mg/m3; SO2 max 0.5 vol%; Ethylene max 500ppm vol; Ozone |
| Available Calibrations | 0-2K, 0-5K, 0-10K, 0-20K |
| Power Supply | 24V nominal supply |
| Example Models | T3031-2-2K-24-P, T3031-2-5K-24-P, T3031-2-10K-24-P, T3032-2-5K-24-P, T3032-2-10K-24-P, T3032-2-20K-24-P |
2411272102_Amphenol-T3032-2-20K-24-P_C1526423.pdf
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible