Online Service

Online Service

Contact Person
+86 136 6733 2386
quality Durable Amphenol T3031-2-5K-24-P CO2 Sensor Featuring IP67 Protection and NDIR Measurement Technology factory
<
quality Durable Amphenol T3031-2-5K-24-P CO2 Sensor Featuring IP67 Protection and NDIR Measurement Technology factory
>
Specifications
Operating Temperature:
0℃~+50℃
Mfr. Part #:
T3031-2-5K-24-P
Key Attributes
Model Number: T3031-2-5K-24-P
Product Description

Product Overview

Telaire T3030 Series CO2 Sensors are designed for accurate CO2 measurement in harsh or difficult environments. These sensors offer a range of combinations for various applications, including HVAC control, incubators, buses, refrigerators, subway stations, railway carriages, and agricultural settings like glass houses and sheds. Featuring Non-Dispersive Infrared (NDIR) measuring technology, they are factory-calibrated and offer a 10-year accuracy guarantee. The series includes options for analog or digital outputs and is rated up to IP67, with optional potting for enhanced protection.

Product Attributes

  • Brand: Amphenol Advanced Sensors Telaire
  • Technology: Non-Dispersive Infrared (NDIR), single or dual wavelength
  • Calibration Guarantee: Lifetime for single wavelength, 2 years for dual wavelength
  • Flammability Classification: To UL94 5VA (dependent upon build)
  • Ingress Protection: Up to IP67, dust tight and immersion to 1m. Optional potting available.
  • Certifications: Tested to Marine, salt mist and particles present; 02 level 0-21 vol%; 0 to 100% RH; Ammonium max 200mg/m3; S02 max 0,5 vol%; Ethylene max 500ppm vol; Ozone. (Note: Not all models are equally capable; discuss application with Telaire.)

Technical Specifications

Specification Details
Product Series T3030 Series
Sensing Method Non-Dispersive Infrared (NDIR), single or dual wavelength
Power Supply Requirements 15 15 VDC 10%, 24 - 18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected
Power Consumption Typical 0.7 W at nominal voltage of 24V AC RMS
Range See Ordering Information for calibrated ranges
Resolution Minimum 10bit or analog equivalent
Accuracy (Single Wavelength, 0~2,000 ppm example) 400-1250 ppm 30 ppm or 3% of reading, whichever is greater*; 1250-2000 ppm 5% of reading + 30ppm *
Accuracy (Dual Wavelength, 0~2,000 ppm example) 75 ppm or 10% of reading (whichever is greater)
Accuracy (Dual Wavelength, 0~200,000 ppm example) 5% of reading or 0.3 vol% CO2 (whichever is larger) at 0 - 20 vol% CO2 and 0C to +25C; At 25C to 50C additional 0.1% of reading or 0.01 vol% CO2 (whichever is larger) per degree C.
Temperature Dependence 0.2% FS / C
Response Time (tau 63%) < 200 sec
Aging (Dual Wavelength Only) +/- 5% of reading annual drift. Less than +/- 25% of reading within product life time.
Recommended Recalibration Interval Single Wavelength No calibration required; Dual Wavelength - 1 year
Working Temperature 0 to +50C (measures within tolerance)
Operation Temperature (Sensor Is Powered) -30 to +50C
Storage Temperature -40 to +70C
Minimum Lifetime 10 years or 30,000 operating hours
RH Range 0% to 99% RH (non-condensing)
Output Configurations Analog: 0 to 5 V, 0 to 10 V, 4 to 20mA; Digital
ABC Logic Self Calibration Employed by single wavelength sensors for automatic background calibration. Requires exposure to ambient reference levels at least three times in 14 days.
Wiring (Power Input and Analog Output) Wire 1: +/~ 24VCC/24VAC; Wire 2: output (4~20mA or 0-10Vdc); Wire 3: -/~ 24VCC/24VAC; Wire 4: Ground
Wiring (Calibration Cable - Deutch Connector) Connection 1: + 5 VDC; Connection 2: Ground; Connection 3: TX UART; Connection 4: RX UART. (Note: ONLY ONE CONNECTION SHOULD BE POWERED AT ANY ONE TIME. POWER INPUT MUST BE OFF WHEN CALIBRATION CABLE IS CONNECTED AND POWERED)
Example Models T3031-2-2K-24-P (Dual Channel, 0-2000 PPM, 0 to 10 VDC o/p, Potted), T3032-2-5K-24-P (Dual Channel, 0-5000 PPM, 4 to 20 mA o/p, Potted)
Other Configurations Available; please contact Telaire. Derivatives include lesser ingress protection, higher fire and smoke ratings, different outputs, and different calibration levels.

2411271924_Amphenol-T3031-2-5K-24-P_C1526452.pdf
Request A Quote

Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible

You Can Upload Up To 5 Files And Each File Sized 10M Max