Specifications
Operating Temperature:
-5℃~+40℃
Mfr. Part #:
VQ2B
Key Attributes
Model Number: VQ2B
Product Description

Product Overview

The VQ2 Combustible Gas Detector Elements are designed for the detection of combustible gases, particularly methane in air mixtures, with concentrations starting from 0.1%. These matched elements offer low power consumption, making them ideal for battery-operated systems. They are unaffected by water vapour or carbon dioxide and provide a minimum sensitivity of 15 mV/% methane when used with the recommended bridge circuit. The VQ2 elements are suitable for operation under direct flow or diffusion conditions.

Product Attributes

  • Brand: SGX Sensortech(IS) Ltd
  • Product Type: Combustible Gas Detector Elements
  • Model Series: VQ2
  • Marking: Serial number in red on detector, black on compensator. Red circular label on detector base.
  • Origin: Registered in England
  • Note: Elements are supplied as a matched pair with a trimming resistor (68-220 ) to be connected across the compensator.

Technical Specifications

Specification Value Notes
Operation Continuous 1
Bridge Supply 2.0 + 0.1 V
Bridge Power Consumption (at 2.0 V) 0.48 W max
Minimum Sensitivity 15 mV/% methane 2
Linearity Linear up to 3% methane
Response Time (to register 1 1/4% in a 2 1/2% concentration) 2 seconds 2, 3
Maximum Methane Concentration 5 % 4
Ambient Temperature Range -75 to +40 C 7
Bridge Zero Change (within temp. range) 1.5 mV max 7
Shock Test 250 g, 5 blows in each plane
Vibration Test 20 g, 24 cycles from 100 to 3200 Hz
Outline Dimension A 11.05 + 0.25 mm
Outline Dimension B 6.10 + 0.25 mm
Outline Dimension C 3.56 + 0.13 mm
Outline Dimension D 63.5 min mm
Outline Dimension E 1.02 mm
Outline Dimension F 7.37 + 0.51 mm
Outline Dimension G 8.20 max mm
Outline Dimension H 9.53 mm
Outline Dimension J 1.52 mm No bends may be made in this length.
Mounting Arrangement AA 19.05 max mm
Mounting Arrangement AB 9.53 + 0.13 mm
Mounting Arrangement AC 8.33 + 0.13 mm
Mounting Arrangement AD 8.20 min mm
Mounting Arrangement AE 19.05 max mm
Mounting Arrangement AF 9.53 + 0.13 mm
Mounting Arrangement AG 8.20 min mm

Notes:
1. Operation may be under either direct flow or diffusion conditions in appropriate mountings.
2. With open-circuit conditions at the bridge output.
3. The response time is a function of the type of mounting used.
4. If the VQ2 is exposed to greater than 5% methane concentration, the calibration of the instrument should be checked.
6. The elements must be protected from certain organic and silicone vapours by suitable filtering, and caution should be exercised when operating in close proximity to hot, oily machinery.
7. The bridge zero shall not change by more than 1.5 mV for this temperature range.


2411261432_Amphenol-VQ2B_C3659385.pdf