Specifications
Operating Temperature:
0℃~+50℃
Mfr. Part #:
T3031-2-2K-24-P
Key Attributes
Model Number:
T3031-2-2K-24-P
Product Description
Product Overview
Telaire T3030 Series CO2 Sensors are designed for accurate CO2 measurement in harsh or difficult environments, offering a robust solution for HVAC control and various industrial applications. These sensors utilize Non-Dispersive Infrared (NDIR) technology and are available with analog or digital output options. Their modular design allows for combinations to meet specific range, supply voltage, and output type needs. Key advantages include easy mounting, high ingress protection ratings (up to IP67), and extended operating temperature ranges. Applications include incubators, buses, refrigerators, subway stations, railway carriages, and agricultural environments like glass houses and animal sheds.Product Attributes
- Brand: Amphenol Advanced Sensors / Telaire
- Sensing Method: Non-Dispersive Infrared (NDIR), single or dual wavelength
- ABC Logic Self Calibration: Available on single wavelength sensors
- Calibration Guarantee: Lifetime for single wavelength, 2 years for dual wavelength
- Flammability Classification: To UL94 5VA (dependent upon build)
- Ingress Protection: Up to IP67 (dust tight and immersion to 1m)
- Optional Feature: Potting available for enhanced protection
Technical Specifications
| Specification | Details |
|---|---|
| Product Series | T3030 Series |
| Power Supply Requirements | 15 15 VDC 10% 24 - 18-30 VAC RMS, 50/60 Hz 18 to 42 VDC, polarity protected |
| Power Consumption | Typical 0.7 W at nominal voltage of 24V AC RMS |
| Range | See Ordering Information for calibrated ranges |
| Resolution | Minimum 10bit or analog equivalent |
| Accuracy (Single Wavelength, 0~2,000 ppm example) | 400-1250 ppm: 30 ppm or 3% of reading, whichever is greater* ** 1250-2000 ppm: 5% of reading + 30ppm *, ** |
| Accuracy (Dual Wavelength, 0~2,000 ppm example) | 75 ppm or 10% of reading (whichever is greater) |
| Accuracy (Dual Wavelength, 0~200,000 ppm example) | 5% of reading or 0.3 vol% CO2 (whichever is larger) at 0 - 20 vol% CO2 and 0C to +25C At 25C to 50C: additional 0.1% of reading or 0.01 vol% CO2 (whichever is larger) per degree C. |
| Temperature Dependence | 0.2% FS / C |
| Response Time (tau 63%) | < 200 sec |
| Aging (Dual Wavelength Only) | +/- 5% of reading annual drift. Less than +/- 25% of reading within product life time. |
| Recommended Recalibration Interval | Single Wavelength No calibration required Dual Wavelength - 1 year |
| Working Temperature | 0 to +50C (measures within tolerance) |
| Operation Temperature (Sensor Is Powered) | -30 to +50C |
| Storage Temperature | -40 to +70C |
| Minimum Lifetime | 10 years or 30,000 operating hours |
| RH Range | 0% to 99% RH (non-condensing) |
| Atmospheric Conditions Tested | Marine, salt mist and particles present; O2 level 0-21 vol%; 0 to 100% RH; Ammonium max 200mg/m3; SO2 max 0.5 vol%; Ethylene max 500ppm vol; Ozone |
| Output Configurations | Analog: 0 to 5 V, 0 to 10 V, 4 to 20mA Digital |
| Analog Output Error | 1% |
| Example Model (Potted) | T3031-2-2K-24-P (Dual Channel, 0-2000 PPM, 0 to 10 VDC o/p, Potted) |
| Example Model (Potted) | T3032-2-5K-24-P (Dual Channel, 0-5000 PPM, 4 to 20 mA o/p, Potted) |
| Example Model (Potted) | T3032-2-10K-24-P (Dual Channel, 0-10,000 PPM, 4 to 20 mA o/p, Potted) |
| Example Model (Potted) | T3032-2-20K-24-P (Dual Channel, 0-20,000 PPM, 4 to 20 mA o/p, Potted) |
2411261406_Amphenol-T3031-2-2K-24-P_C1526446.pdf
Request A Quote
Please Use Our Online Inquiry Contact Form Below If You Have Any Questions, Our Team Will Get Back To You As Soon As Possible