Operating Temperature:
0℃~+50℃
Mfr. Part #:
T3031-2-10K-24-P
Key Attributes
Model Number: T3031-2-10K-24-P
Product Description

T3030 Series CO2 Sensors for Harsh Environments with Analog Outputs

Product Overview

The Amphenol Advanced Sensors Telaire T3030 Series offers a range of Carbon Dioxide (CO2) sensors specifically engineered for harsh or difficult environments. These accurate CO2 transmitters are designed for HVAC control applications and feature easy mounting with two external tabs. With ratings up to IP67 (build dependent) and optional potting, these sensors are suitable for demanding applications such as incubators, buses, refrigerators, subway stations, railway carriages, and agricultural settings like glass houses, mushroom sheds, and animal sheds. The T3030 Series utilizes Non-Dispersive Infrared (NDIR) measuring technology and is available with various calibrations up to 20% CO2 concentration, offering analog or digital output options. Sensors are factory-calibrated and designed for a 10-year life with an extended operating temperature range.

Product Attributes

  • Brand: Amphenol Advanced Sensors Telaire
  • Sensing Method: Non-Dispersive Infrared (NDIR), single or dual wavelength
  • Accuracy Guarantee: Lifetime calibration guarantee for single wavelength sensors; two-year calibration guarantee for dual wavelength sensors.
  • Flammability Classification: To UL94 5VA (dependent upon build)
  • ABC Logic Self Calibration: Patented system for single wavelength sensors to virtually eliminate the need for manual calibration in typical indoor environments.

Technical Specifications

Specification Details
Power Supply Requirements 15 15 VDC 10%
24 - 18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected
Power Consumption Typical 0.7 W at nominal voltage of 24V AC RMS
Range See Ordering Information for calibrated ranges
Resolution Minimum 10bit or analog equivalent
Accuracy (Single Wavelength, 0~2,000 ppm example) 400-1250 ppm 30 ppm or 3% of reading, whichever is greater*
1250-2000 ppm 5% of reading + 30ppm *
Accuracy (Dual Wavelength, 0~2,000 ppm example) 75 ppm or 10% of reading (whichever is greater)
Accuracy (Dual Wavelength, 0~200,000 ppm example) 5% of reading or 0,3 vol% CO2 (whichever is larger) at 0 - 20 vol% CO2 and 0C to +25C
At 25C to 50C additional 0,1% of reading or 0,01 vol% CO2 (whichever is larger) per degree C.
Temperature Dependence 0.2% FS / C
Response Time (tau 63%) < 200 sec
Aging (Dual Wavelength Only) +/- 5% of reading annual drift. Less than +/- 25% of reading within product life time.
Recommended Recalibration Interval Single Wavelength No calibration required
Dual Wavelength - 1 year
Working Temperature 0 to +50C (measures within tolerance)
Operation Temperature (Sensor Is Powered) -30 to +50C
Storage Temperature -40 to +70C
Minimum Lifetime 10 years or 30,000 operating hours
RH Range 0% to 99% RH (non-condensing)
Atmospheric Conditions (Tested) Marine, salt mist and particles present; 02 level 0-21 vol%; 0 to 100% RH; Ammonium max 200mg/m3; S02 max 0,5 vol%; Ethylene max 500ppm vol; Ozone
IP Class Up to IP67, dust tight and immersion to 1m. Optional potting available.
Output Configurations Analog: 0 to 5 V, 0 to 10 V, 4 to 20mA
Digital
Error (Analog Output) 1%
Wiring (Power Input and Analog Output) Wire 1 +/~ 24VCC/24VAC
Wire 2 output, 4~20mA or 0-10Vdc
Wire 3 -/~ 24VCC/24VAC
Wire 4 Ground
Wiring (Calibration Cable - Deutch Connector) Connection 1 + 5 VDC
Connection 2 Ground
Connection 3 TX UART
Connection 4 RX UART
Model Examples T3031-2-2K-24-P (Dual Channel, 0-2000 PPM, 0-10V o/p, Potted)
T3031-2-5K-24-P (Dual Channel, 0-5000 PPM, 0-10V o/p, Potted)
T3031-2-10K-24-P (Dual Channel, 0-10,000 PPM, 0-10V o/p, Potted)
T3032-2-5K-24-P (Dual Channel, 0-5000 PPM, 4-20mA o/p, Potted)
T3032-2-10K-24-P (Dual Channel, 0-10,000 PPM, 4-20mA o/p, Potted)
T3032-2-20K-24-P (Dual Channel, 0-20,000 PPM, 4-20mA o/p, Potted)
Available Calibrations 0-2K, 0-5K, 0-10K, 0-20K
Output Options Digital (Modbus, UART), Analog (0-5V, 0-10V, 4-20mA)